1" FPT Caleffi Quicksetter Balancing Valve with Flow Meter & Insulating Shell

SKU:
GF-VQS4F
$217.20
NON-STOCK:
2-3 WEEK LEAD TIME
Adding to cart… The item has been added

1" FPT Caleffi Quicksetter Balancing Valve with Flow Meter & Insulating Shell

Specifications:

  • Connection Size 1"
  • Flow Rate Range - 3.0-10 GPM
  • Heat Pump Nominal Tons (Closed Loop) - 1-3
  • Heat Pump Nominal Tons (Open Loop) - 2-6
  • Valve Cv- 8.3
  • Pressure Drop - 2.7ft-hd @ 9 GPM

Notes:

  • Valves should be selected based on the required flow rate, not connection size.  For example, if you have a 5-ton heat pump with 1” connections, you should select the VQS5F and use a reducing fitting to go from 1-1/4” to 1”.
  • The flow rate range for each valve overlaps the next size up; chose the valve that is closest to the pipe size you are using. In some cases you may chose to use all the same size valve on a job even when a smaller one will work for simplicity. For example, you may use the 1-1/4″ VQS5F for 2 ton units when you also have 4 ton and 5 ton units installed so that you can use one valve size for every unit on the job.
  • This recommendation is for closed loop systems with a nominal flow rate of 3 GPM per ton.  Check the heat pump manufacturer’s literature for actual recommended flow rate.
  • This recommendation is for open loop systems with a nominal flow rate of 1.5 GPM per ton.  Check the heat pump manufacturer’s literature for actual recommended flow rate.
  • Pressure drop assumes water and is provided at the flow rate for the maximum Geo-Flo recommended nominal tonnage.  When using an antifreeze solution either use Cv to calculate pressure drop or apply the appropriate antifreeze correction factor.
  • For flow rates or sizes not listed, contact us.